Arc flash incidents are among the most dangerous electrical hazards in industrial facilities, capable of causing severe injuries or fatalities in a fraction of a second. Understanding arc flash hazards and implementing effective prevention and mitigation strategies is critical for protecting workers and maintaining safe operations. This guide provides practical insights for electrical safety professionals and facility managers.
What is an Arc Flash?
An arc flash is an explosive release of energy caused by an electric arc. When an electrical fault creates an arc through air between conductors or from conductor to ground, the resulting plasma arc can reach temperatures exceeding 35,000°F—hotter than the surface of the sun. The intense heat, pressure wave, molten metal spray, and blinding light pose multiple hazards to nearby workers.
Arc Flash Versus Arc Blast
While often used interchangeably, these terms describe different aspects of the same event. The arc flash refers to the thermal hazard from radiant energy, while the arc blast describes the pressure wave that can throw workers against walls or equipment. Both hazards must be addressed in protection strategies.
- •Arc flash: Thermal energy causing severe burns
- •Arc blast: Pressure wave causing physical trauma
- •Sound blast: Noise levels potentially causing hearing damage
- •Molten metal: Ejection of superheated droplets
- •Intense light: Temporary or permanent vision damage
Common Causes
Arc flash incidents result from various causes, many of which are preventable through proper procedures and maintenance. Understanding these causes helps organizations implement effective prevention strategies.
- •Accidental contact with energized components
- •Dust or corrosion creating conductive paths
- •Dropping tools across energized conductors
- •Improper work procedures near energized equipment
- •Equipment failure due to insulation breakdown
- •Animals or foreign objects bridging conductors
Incident Energy and Hazard Boundaries
Arc flash hazard assessment involves calculating incident energy levels and establishing appropriate boundaries for safety. These calculations determine the thermal energy a worker might receive at various distances from a potential arc flash.
Incident Energy Calculations
Incident energy, measured in calories per square centimeter (cal/cm²), depends on available fault current, clearing time, working distance, and system voltage. IEEE 1584 provides the most widely used calculation methods, with different equations for various voltage levels and equipment configurations.
- •Available fault current at the point of work
- •Protective device clearing time
- •Working distance from arc source
- •Equipment configuration and enclosure type
- •System voltage and grounding configuration
Arc Flash Boundary
The arc flash boundary is the distance at which incident energy equals 1.2 cal/cm²—the threshold where a worker could receive a second-degree burn. Within this boundary, workers must wear appropriate arc-rated personal protective equipment (AR PPE) and follow safe work practices.
- •Calculated for each piece of electrical equipment
- •Displayed on equipment labels with PPE requirements
- •Used to establish restricted access during energized work
- •Varies with equipment type, voltage, and protection settings
- •Must be recalculated when system conditions change
Risk Assessment and Analysis
Comprehensive arc flash risk assessment is the foundation of an effective electrical safety program. This process identifies hazards, calculates incident energy levels, and determines appropriate protective measures for workers.
Arc Flash Study Process
A thorough arc flash hazard analysis follows a systematic process including data collection, short circuit analysis, protective device coordination, and incident energy calculations. The study results in equipment labels and documentation supporting safe work procedures.
- •Gather electrical system data and single-line diagrams
- •Perform short circuit analysis to determine fault currents
- •Review protective device settings and coordination
- •Calculate incident energy and arc flash boundaries
- •Determine PPE categories for each equipment location
- •Generate arc flash warning labels
- •Document findings and recommendations
Factors Affecting Arc Flash Hazard
Several system factors significantly influence arc flash hazard levels. Understanding these factors helps engineers identify opportunities to reduce incident energy through system modifications.
- •Available fault current (higher current = more energy)
- •Protective device clearing time (longer time = more energy)
- •Working distance (greater distance = less energy exposure)
- •Equipment enclosure type affecting arc development
- •System voltage influencing arc sustainability
- •Upstream coordination requirements affecting clearing time
Mitigation Strategies
Reducing arc flash hazards improves worker safety and may reduce insurance costs and compliance burdens. Multiple strategies exist for mitigation, often used in combination for maximum effectiveness.
Engineering Controls
Engineering solutions that reduce incident energy or eliminate exposure to energized equipment are the most effective mitigation approaches. These should be prioritized according to the hierarchy of controls.
- •De-energization: Working on equipment in an electrically safe condition
- •Remote operation: Performing switching operations from outside arc flash boundary
- •Current limiting: Using fuses or current-limiting breakers
- •Zone-selective interlocking: Reducing fault clearing time
- •Arc flash relay systems: Detecting and rapidly clearing arcs
- •Reduced-energy maintenance mode: Implementing lower settings during maintenance
- •Equipment replacement: Upgrading to arc-resistant or safer designs
Administrative Controls
Procedures, training, and work practices form critical layers of protection when engineering controls cannot eliminate hazards. These controls require consistent implementation and enforcement.
- •Energized electrical work permits
- •Job briefings before work on or near energized equipment
- •Qualified person requirements and training
- •Lockout/tagout procedures
- •Approach boundaries and restricted access
- •Regular equipment maintenance to prevent failures
- •Incident investigation and lessons learned
Personal Protective Equipment
Arc-rated PPE provides the last line of defense when workers must be within the arc flash boundary. Proper selection, use, and maintenance of PPE is essential for worker protection.
- •Arc-rated clothing appropriate for incident energy level
- •Arc-rated face shields and safety glasses
- •Insulating rubber gloves with leather protectors
- •Hearing protection for arc blast noise
- •Leather or arc-rated gloves for thermal protection
- •Proper layering system for required arc rating
- •Regular inspection and replacement of damaged PPE
Compliance and Best Practices
Compliance with NFPA 70E and industry best practices is both a legal requirement and an ethical obligation. Establishing a culture of electrical safety requires commitment at all organizational levels.
NFPA 70E Requirements
NFPA 70E establishes the standard of care for electrical safety in the workplace. Understanding and implementing these requirements is essential for compliance and worker protection.
- •Electrical Safety Program including procedures and training
- •Hazard identification and risk assessment
- •Safety-related work practices including de-energization
- •PPE selection and use requirements
- •Lockout/tagout procedures
- •Arc flash hazard analysis and equipment labeling
- •Training and qualification requirements for electrical workers
Program Continuous Improvement
An effective electrical safety program requires ongoing evaluation and improvement. Regular reviews ensure the program remains current with standards, technology, and organizational changes.
- •Annual electrical safety program review
- •Update arc flash studies after significant system changes
- •Review incident and near-miss reports for lessons learned
- •Track leading indicators like energized work permits and job briefings
- •Benchmark against industry best practices
- •Engage workers in safety improvement initiatives
- •Stay current with standards updates and new technologies
Final Thoughts
Arc flash hazards pose serious risks in industrial facilities, but these risks can be effectively managed through comprehensive hazard assessment, engineering controls, administrative procedures, and appropriate PPE. Organizations that prioritize arc flash safety protect their most valuable asset—their people—while reducing liability and demonstrating commitment to safety excellence. Implementing and maintaining a robust electrical safety program aligned with NFPA 70E requirements is both a regulatory obligation and a moral imperative. Need help assessing arc flash hazards or developing your electrical safety program? Contact our safety experts today.