Full Load Current Calculator
Calculate full load current for various electrical equipment including motors, transformers, and general loads.
Formulas Used
Single Phase Motor: I = (HP × 746) / (V × Eff × PF)
Three Phase Motor: I = (HP × 746) / (√3 × V × Eff × PF)
Three Phase General: I = kW × 1000 / (√3 × V × PF)
Three Phase Resistive: I = kW × 1000 / (√3 × V)
Notes
- Motor efficiency typically ranges from 0.85 to 0.95 for standard motors
- Power factor typically ranges from 0.8 to 0.95 for inductive loads
- Use 1.0 power factor for resistive loads (heaters, incandescent lighting)
- Per NEC 430.6, use motor nameplate current when available
- Conductors must be sized at 125% of full load current (NEC 430.22)