3 Phase Power Calculator: kW, kVA, and Full Load Current
A free 3 phase power calculator for kW, kVA, and kVAR; full load current of motors, transformers, and heaters; and three phase voltage imbalance per NEMA MG-1. Use it to size feeders, check measured loads against nameplate, or verify a balanced three-phase system before energizing.
3 phase power formula
V is line-to-line voltage, I is line current, pf is power factor, and √3 ≈ 1.732. Example: a 480 V load drawing 100 A at 0.9 pf uses √3 × 480 × 100 × 0.9 ÷ 1000 = 74.8 kW (83.1 kVA).
Need amps instead? Use the 3 phase current calculator. Adding up a panel? Use the 3 phase load calculation tool. Checking imbalance? Use the current unbalance calculator.
Three-Phase Power Calculations
Calculate power relationships in balanced three-phase systems
Need this validated by a licensed PE?
A free calculator gets you in the ballpark. For permit-stamped, defensible work, ClarkTE delivers a PE-stamped three-phase load and feeder study from a working engineer, based on your one-line and load data.
What is three phase power?
Three phase power is an AC distribution system that uses three sinusoidal voltages, each offset by 120 degrees, instead of a single waveform. The three phases combine in a way that delivers power continuously rather than in pulses, which is why almost every motor over a few horsepower runs on three phase.
In North American commercial and industrial buildings the most common three phase voltages are 208Y/120 V (small commercial), 480Y/277 V (most industrial), and 600Y/347 V (Canadian industrial). The "Y" denotes a wye-connected secondary; the slash separates the line-to-line voltage from the line-to-neutral voltage, and the relationship between them is the √3 factor that shows up in every three phase formula.
Why does the √3 matter? Because when you measure the three line currents, each is in phase with its own line-to-neutral voltage but not with the line-to-line voltage you usually use as the system label. The √3 (≈1.732) bridges the two. That's the entire reason kVA = √3 × V_LL × I and kW = √3 × V_LL × I × power factor.
Three phase formulas you'll actually use
| What you want | Formula | Notes |
|---|---|---|
| Apparent power S | S (kVA) = √3 × V_LL × I / 1000 | Always positive |
| Active power P | P (kW) = √3 × V_LL × I × pf / 1000 | Multiply by power factor |
| Reactive power Q | Q (kVAR) = √(S² − P²) | Or S × sin(arccos pf) |
| Line current from kW | I = (kW × 1000) / (√3 × V_LL × pf) | Inverse of P formula |
| Motor FLA from HP | I = (HP × 746) / (√3 × V × η × pf) | Use NEC 430.250 for design |
| Voltage imbalance | % = (max deviation / avg) × 100 | Keep ≤ 1% per NEMA MG-1 |
Three-phase systems behaving badly?
If you're seeing voltage imbalance over 2%, repeat motor failures, or unexplained heating in feeders, ClarkTE's protection and control team can do a power quality study, root-cause analysis, and produce a PE-stamped recommendations report.
Three-phase power FAQ
What is three-phase power?
Three-phase power uses three sinusoidal voltages each offset by 120 degrees. The phases combine to deliver power continuously rather than in pulses, which is why almost every motor over a few horsepower runs on three-phase. Common North American three-phase voltages are 208Y/120 V, 480Y/277 V, and 600Y/347 V.
How do I convert kW to amps for a three-phase load?
I = (kW × 1000) / (√3 × V_LL × pf). The √3 factor (≈1.732) comes from the 120° phase relationship between line voltages. The Power Calculations tab returns the line current directly when you enter kW and power factor.
What's the limit on three-phase voltage imbalance?
NEMA MG-1 recommends voltage imbalance ≤ 1%. Above 2%, motors must be derated to avoid overheating. The Unbalanced Loads tab calculates imbalance as (max deviation from average / average) × 100% and flags marginal/poor results.
Want to do this for a living?
If you are running three-phase loads by hand, you already have the instincts. ClarkTE trains technicians and test engineers on the equipment these numbers describe — taught by working engineers, not a content mill.
See the training trackRelated ClarkTE calculators
Apparent power to full load current, three-phase or single-phase.
Measured current to real power, with kVA and kVAR alongside.
Line and phase voltage and current for both configurations.
What differs, and how much current each draws for the same load.
Sizing, kVA selection, primary/secondary current, and fault current.
Size capacitor banks to lift PF on three-phase systems.